System data | PROFIBUS DP | IPxxxx-B31x, IL230x-B31x, IL230x-C31x |
---|
Number of I/O stations | 100 with repeater |
Number of I/O points | approx. 6,000, depending on the master |
Data transfer medium | shielded copper cable, 2 x 0.25 mm² |
Distance between stations | 1,200 m | 1,000 m | 400 m | 200 m | 100 m |
|
Data transfer rates | 9.6/19.2/
93.75 kbaud | 187.5 kbaud | 500 kbaud | 1,500 kbaud | …3/6/12 Mbaud |
|
Data transfer time | approx. 0.5 ms with 10 stations each with 32 bit input and output |
Technical data | IPxxxx-B310 | IPxxxx-B318 | IL230x-B310, -C310 | IL230x-B318, -C318 |
---|
Extension modules | – | – | max. 120 with max. 128 byte input and 128 byte output data | max. 120 with max. 128 byte input and 128 byte output data |
Digital peripheral signals | according to I/O type | according to I/O type | max. 960 inputs and 960 outputs | max. 960 inputs and 960 outputs |
Analog peripheral signals | according to I/O type | according to I/O type | max. 60 inputs and 60 outputs | max. 60 inputs and 60 outputs |
Configuration possibility | via KS2000 or the controller, DP-V1 extensions are supported |
Data transfer rates | automatic detection up to 12 Mbaud |
Bus connection (B-coded) | 1 x M12 socket, 5-pin | 1 x M12 socket, 5-pin, 1 x M12 plug, 5-pin (tee-connector integrated) | 1 x M12 socket, 5-pin | 1 x M12 socket, 5-pin, 1 x M12 plug, 5-pin (tee-connector integrated) |
Power supply | control voltage: 24 V DC (-15 %/+20 %); load voltage: according to I/O type |
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Box supply current | 85 mA + current consumption of sensors, max. 0.5 A |
Auxiliary power current | according to I/O type |
Electrical isolation | control voltage/fieldbus: no, control voltage/inputs or outputs: according to I/O type |
Weight | approx. 210 g | approx. 250 g | approx. 210 g | approx. 250 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals | CE, UL |