Регистрация
deal.by
IPxxxx-, IL230x-B/C31x | Fieldbus Box modules for PROFIBUS - фото 1 - id-p101663726
Характеристики и описание

Техническая спецификация в PDF    

System dataPROFIBUS DP | IPxxxx-B31x, IL230x-B31x, IL230x-C31x
Number of I/O stations100 with repeater
Number of I/O pointsapprox. 6,000, depending on the master
Data transfer mediumshielded copper cable, 2 x 0.25 mm²
Distance between stations
1,200 m1,000 m400 m200 m100 m
Data transfer rates
9.6/19.2/­

93.75 kbaud
187.5 kbaud500 kbaud1,500 kbaud…3/6/12 Mbaud
Data transfer timeapprox. 0.5 ms with 10 stations each with 32 bit input and output

Technical dataIPxxxx-B310IPxxxx-B318IL230x-B310, -C310IL230x-B318, -C318
Extension modulesmax. 120 with max. 128 byte input and 128 byte output datamax. 120 with max. 128 byte input and 128 byte output data
Digital peripheral signalsaccording to I/O typeaccording to I/O typemax. 960 inputs and 960 outputsmax. 960 inputs and 960 outputs
Analog peripheral signalsaccording to I/O typeaccording to I/O typemax. 60 inputs and 60 outputsmax. 60 inputs and 60 outputs
Configuration possibilityvia KS2000 or the controller, DP-V1 extensions are supported
Data transfer ratesautomatic detection up to 12 Mbaud
Bus connection (B-coded)1 x M12 socket, 5-pin1 x M12 socket, 5-pin, 1 x M12 plug, 5-pin (tee-connector integrated)1 x M12 socket, 5-pin1 x M12 socket, 5-pin, 1 x M12 plug, 5-pin (tee-connector integrated)
Power supplycontrol voltage: 24 V DC (-15 %/+20 %); load voltage: according to I/O type
Power supply connectionfeed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Box supply current85 mA + current consumption of sensors, max. 0.5 A
Auxiliary power currentaccording to I/O type
Electrical isolationcontrol voltage/fieldbus: no, control voltage/inputs or outputs: according to I/O type
Weightapprox. 210 gapprox. 250 gapprox. 210 gapprox. 250 g
Operating/storage temperature0…+55 °C/-25…+85 °C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.IP 65/66/67 (conforms to EN 60529)/variable
ApprovalsCE, UL

Accessories
KS2000configuration software for extended parameterisation
TX1200programming system conforms to IEC 61131-3
Cordsetscordsets and connectors

System
PROFIBUSFor further PROFIBUS products please see the system overview.

IPxxxx-B310|B318Compact Box for PROFIBUS DP systems (12 Mbaud)Plug
Digital input
IP1000-B310|B318
Был online: Давно
OOO "ФилФар Технолоджи"
Рейтинг не сформирован
10 лет на Deal.by

IPxxxx-, IL230x-B/C31x | Fieldbus Box modules for PROFIBUS

Под заказ
Цену уточняйте
Доставка
Оплата и гарантии

У нас покупают

IPxxxx-, IL230x-B/C31x | Fieldbus Box modules for PROFIBUS в Червени